1) Conductor: Soft annealed copper stranded as per class 5 of IEC 60228, ISIRI 3084
2) Insulation: Polyvinyl chloride (PVC)
3) outer sheath: Polyvinyl chloride (PVC). Colour can be supplied on request.

 

NYMHY
Application
These cables can be used indoor or outdoor in cable ducts or trays in power and switching stations, industrial plants and commercial buildings. Suitable for direct burial where there is no danger of mechanical damage.
Construction
1) Conductor: Soft annealed copper stranded as per class 5 of IEC 60228, ISIRI 3084
2) Insulation: Polyvinyl chloride (PVC)
3) Core identification: colour
4) Inner covering: Extruded PVC compatible with the operating temperature of the conductor. This inner covering is applicable to cables with conductors of 16 mm2 or above.
5) outer sheath: Polyvinyl chloride (PVC). Colour can be supplied on request.
Specification IEC 60502, ISIRI 3569
Technical data
1) Temperature: -25oC to +80oC
2) Maximum short circuit temperature: 160oC (5 seconds Max.)
3) Working voltage: 0.6/0.1 kv
4) Conductor resistance: As per class 5 of IEC 60228, ISIRI 3084
5) Test voltage: 3.5 kv rms or 8.4 kvdc for 5 minutes.
6) Flame retardant: Acc. IEC 60332-1
More Info
NYMHY

Approx.

weight

Approx.

Overall

diameter

Sheath

thickness

Insulation

thickness

No.

strand x

diameter

Size

Kg/Km

mm

mm

mm

N × d mm

mm2

134

10

1.8

0.8

30×0.25

2×1.5

174

11

1.8

0.8

50×0.25

2×2.5

221

12

1.8

1.0

56×0.3

2×4

284

13.2

1.8

1.0

84×0.3

2×6

460

15.8

1.8

1.0

80×0.4

2×10

660

17.8

1.8

1.0

127×0.4

2×16

1150

25.4

1.8

1.2

199×0.4

2×25

1470

28

1.8

1.2

278×0.4

2×35

1990

32.5

2.0

1.4

398×0.4

2×50

2700

37

2.1

1.4

357×0.5

2×70

NYMHY

Approx.

weight

Approx.

Overall

diameter

Sheath

thickness

Insulation

thickness

No.

strand x

diameter

Size

mm

mm

mm

mm

N × d mm

mm2

132

10.5

1.8

0.8

30×0.25

3×1.5

204

11.5

1.8

0.8

50×0.25

3×2.5

270

12.7

1.8

1.0

56×0.3

3×4

360

14

1.8

1.0

84×0.3

3×6

540

16.8

1.8

1.0

80×0.4

3×10

756

19

1.8

1.0

127×0.4

3×16

1350

26

1.8

1.2

199×0.4

3×25

1790

30

1.9

1.2

278×0.4

3×35

2500

35

2.0

1.4

398×0.4

3×50

3240

39.5

2.2

1.4

357×0.5

3×70

4400

45.6

2.4

1.6

484×0.5

3×95

5400

50

2.5

1.6

612×0.5

3×120

6700

55.6

2.7

1.8

765×0.5

3×150

Approx.

weight

Approx.

Overall

diameter

Sheath

thickness

Insulation

thickness

No.

strand x

diameter

Size

mm

mm

mm

mm

N × d mm

mm2

1520

28

1.9

1.2 – 1.0

199×0.4 - 127×0.4

3×25/16

1940

31

2.0

1.2 – 1.0

278×0.4 - 127×0.4

3×35/16

2700

36.2

2.1

1.4 – 1.2

398×0.4 - 199×0.4

3×50/25

3650

41

2.3

1.4 – 1.2

357×0.5 - 278×0.4

3×70/35

4800

47

2.5

1.6 – 1.4

484×0.5 - 398×0.4

3×95/50

6060

52.4

2.6

1.6 – 1.4

612×0.5 - 357×0.5

3×120/70

7340

58.4

2.8

1.8 – 1.4

765×0.5 - 357×0.5

3×150/70

Approx.

weight

Approx.

Overall

diameter

Sheath

thickness

Insulation

thickness

No.

strand x

diameter

Size

mm

mm

mm

mm

N × d mm

mm2

185

11.3

1.8

0.8

30×0.25

4×1.5

246

12.4

1.8

0.8

50×0.25

4×2.5

325

13.8

1.8

1.0

56×0.3

4×4

425

15.2

1.8

1.0

84×0.3

4×6

670

18.4

1.8

1.0

80×0.4

4×10

950

20.8

1.8

1.0

127×0.4

4×16

1670

29

1.9

1.2

199×0.4

4×25

2220

32.6

2.0

1.2

278×0.4

4×35

3070

38.4

2.2

1.4

398×0.4

4×50

4130

43.8

2.4

1.4

357×0.5

4×70

5480

50

2.6

1.6

484×0.5

4×95

6860

54.8

2.7

1.6

612×0.5

4×120

8540

61

2.9

1.8

765×0.5

4×150

 

Tags: